:: Signal Isolator ( Multiple Input, Multiple Output )

  • Time Proven High Precision Electronic Design
  • Manufacturing & Supplying since last 14 years
  • Accuracies upto 0.1% also achievable
  • Upto & Galvanic Isolators
  • ???? of 1500V DC
  • Input : Predefined
  • O/P : Predefined, Max 4 nos.
  • Lan incorporate Non-Standard Signal I/P <- O/P
  • Display / Bar graph facility optional
  • 230V AC / 110V AC / 24V DC
  • DIN RAIL & WALL mount enclosure
  • Supplying to the most reputed names like ABB, Alstan, GAIL, Grasim, Dept. of Atomic Energy, Atomic Power Stations and many others
  • Totally service / maintenance free
  • max 3 i/p, 30/p possible

> Introduction ::

Pantech's Multiple Input Signal Isolator, model 831 is an ideal instrument for accepting various types of inputs from field and feed the converted signals to a control room instruments accepting upto three standard inputs. Input to the Isolator can be from thermocouple, RTD, two-wire transmitter, non two-wire transmitter, mV or a voltage source.

The instrument accepts upto three inputs in any combination and range, and provides corresponding isolated outputs of 4 – 20 mA DC/ 1 – 5 V DC. All the three inputs are isolated with each other and outputs. This enables the use of grounded thermocouples, guards against leakage resistance and simplifies selection of safety barriers. All outputs have common zero, which further simplifies use of any receiver instrument without much of a problem.

The instrument is powered from 24V DC, 110V AC or 230V AC power source.

Low drift precession components are used for long term accuracy of the instruments. All instruments undergo a burn-in for better reliability.

The instrument can be mounted on a wall or back of panel, its terminations are provided in front.

> Specifications ::

Input

1) Current, 4 - 20 mA DC/ 0 - 20 mA DC
2) Voltage, 1 - 5 V DC/ 0 - 10 V DC
3) RTD Pt 100
4) T/C Type J, K, R, S, T.

Input impedance


200 K for Voltage, mV & T/C inputs
250 for current inputs

Cold junction compensation

Built in for T/C input.

Isolation

Between input, each of outputs and power supply

Analog output

1) Isolated 4 - 20 mA DC / 0 - 20 mA DC
2) Isolated 1 - 5 V DC / 0 - 5 V DC

Analog output load capability

800 maximum for current o/p.

Output accuracy

+/- 0.25% of span

Display accuracy


+/- 0.1% of span

Transmitter power

24 V DC for current inputs

Power supply

1) 24 V DC
2) 110 V AC, 50 Hz, +/- 10%
3) 230 V AC, 50 Hz, +/- 10%

Power consumption

6 VA max.

Ambient temperature

0 - 50° C.

Storage temperature

0 - 70° C.

Humidity

90% RH (non-condensing)

Please have a look at the following table to understand the availability of different sizes.

Mounting
Dimension
Inputs
Power
Type of o/p
Np. of i/p
Panel
96 * 96 * 150
All
All
All
Max. 3
Din
70 * 100 * 110
All
All
All
Max. 2
Wall
195 * 70 * 115
All
All
All
Max. 3
EURO
130 * 20 * 120
All
24V DC
All
Max. 2