:: Electronic / Difference / Averaging
Indicator Cum Controller ( Model 806 )
|
1. |
Analog based electronics |
2.
|
Input
: 2 nos. predefined |
3. |
O/P
: Diff. / Avg. of µP |
4. |
Contacts
: Optional |
5.
|
Accuracy
: +/- 0.1 % of span |
6. |
Retransmission
(Optional) Isolated / Non Isolated 4 - 20 mA |
7.
|
Trusted
& used by hundreds of industrial giants through
out country. |
|
>
Introduction
::
Pantech's
Difference/Averaging Indicator cum
Controller, model 806 is an ideal instrument for
providing indication as well as controlling set points on difference/average
of two processes. It is designed to accept various process inputs
(Current, Voltage, RTD, and Thermocouple), display the same and
generate potential free contacts on either individual process or
difference/average of two processes when abnormal conditions occur.
The model is equipped with an optional analog output facility (Isolated
or non-isolated).
Model
806 is an analog electronics based controller. It is capable to
display the process value to the resolution of maximum 3 ½
digits and can be designed to generate maximum of 4 nos. of potential
free contacts. A further virtue of the controller is that alarms
can be field configurable (i.e. HIGH “or” LOW) and adjustable.
Hysteresis (deadband) can be varied from 1% to 15% of span. It is
also facilitated with internal transmitter power supply of 24 V
DC, to power up two-wire transmitters.
Low drift precession components are used for long term accuracy
of the instruments. All instruments undergo a burn-in for better
reliability.
>
Specifications
::
Input
1) Current, 4 - 20 mA DC/ 0 - 20 mA DC
2) Voltage, 1 - 5 V DC/ 0 - 10 V DC
3) RTD Pt 100
4) T/C Type J, K, R, S, T.
Input impedance
200 K for
Voltage, mV & T/C inputs
250 for current
inputs
Cold
junction compensation
Built
in for T/C input.
Alarms
Maximum 4 nos. of potential free contacts.
Analog output
1) Isolated 4 - 20 mA DC
2) Non isolated 4 - 20 mA DC
Analog output
load capability
800 maximum
Output accuracy
+/- 0.25% of span |
Display
accuracy
+/- 0.1% of span
Transmitter
power
24 V DC for current inputs
Power supply
1) 24 V DC
2) 110 V AC, 50 Hz, +/- 10%
3) 230 V AC, 50 Hz, +/- 10%
Contact ratings
230 V AC, 5 Amps.
Power consumption
6 VA max.
Ambient temperature
0 - 50° C.
Storage
temperature
0 - 70° C.
Humidity
90% RH (non-condensing)
|
Please
have a look at the following table to understand the availability
of different sizes.
Mounting |
Dimension |
Inputs
Current /
Voltage /
RTD / Th. |
Power
230V AC /
24V DC /
110V AC |
Alarms |
Isolated
4 - 20 mA
Retransmission |
Non
Isolated
4 - 20 mA
Retransmission |
Display
|
Panel |
96
* 96 * 225 |
All |
All |
Max.
4 |
Yes |
Yes |
3
½
digit,
½"
size
|
96
* 96 * 150 |
All |
All |
Max.
2 |
Yes |
Yes |
3
½
digit, ½"
size
|
72
* 144 * 200 |
All |
All |
Max.
2 |
Yes |
Yes |
3
½
digit, ½"
size |
Back
|