1.
Microcontroller based electronics
2.
Input : Universal ( Current, Voltage, RTD. / Th. )
3.
Ranges : Field acceptable / through front 4 keys
4.
Accuracy : +/- 0.1 % of span
5.
Retransmission (Optional) Isolated / Non Isolated 4 - 20 mA
6.
Available in large display sizes (up to 16")
7.
Trusted & used by hundreds of industrial giants through out country.

> Introduction ::

Pantech's Universal Indicator cum Controller, model 802 is an ideal instrument for providing indication as well as controlling set points to various processes. It is designed to accept various process inputs (Current, Voltage, RTD, and Thermocouple) simultaneously with all inputs onboard field configurable and display the same, generate potential free contacts when abnormal conditions occur. The model is equipped with an optional analog output facility (Isolated or non-isolated).

Model 802 is a Microcontroller-based controller. It is capable to display the process value to the resolution of maximum 4 digits and can be designed to generate maximum of 4 nos. of potential free contacts. A further virtue of the controller is that alarms can be field configurable (HIGH “or” LOW) and adjustable. Hysteresis (deadband) can be varied from 1% to 99% of span. It is also facilitated with internal transmitter power supply of 24 V DC, to power up two-wire transmitters. It can be optionally equipped with serial communication facility of different open protocols. Again optional centronic printer port with escape commands (for dot matrix printers) can be provided to get direct printer output.

Low drift precession components are used for long term accuracy of the instruments. All instruments undergo a burn-in for better reliability.

> Specifications ::

Input

1) Current, 4 - 20 mA DC/ 0 - 20 mA DC
2) Voltage, 1 - 5 V DC/ 0 - 10 V DC
3) RTD Pt 100
4) T/C Type J, K, R, S, T.

Input impedance


200 K for Voltage, mV & T/C inputs
250 for current inputs

Alarms

Maximum 4 nos. of potential free contacts.

Analog output

1) Isolated 4 - 20 mA DC
2) Non isolated 4 - 20 mA DC

Analog output load capability

800 maximum

Output accuracy


+/- 0.25% of span

Serial output with open protocol

1) RS232 With modbus RTU or ASCII protocol
2) RS485 with modbus RTU or ASCII protocol
Note: Any other protocol on demand

Parallel output port
1) Compatible with Escape command format
Note: Any other protocol on demand

Display accuracy


+/- 0.1% of span

Transmitter power

24 V DC for current inputs

Power supply

1) 24 V DC
2) 110 V AC, 50 Hz, +/- 10%
3) 230 V AC, 50 Hz, +/- 10%

Contact ratings

230 V AC, 5 Amps.

Power consumption

3 VA max.

Ambient temperature

0 - 50° C.

Storage temperature

0 - 70° C.

Humidity

90% RH (non-condensing)

Please have a look at the following table to understand the availability of different sizes.

Mounting
Dimension
Inputs Current /
Voltage /
RTD / Th.
Power
230V AC /
24V DC /
110V AC
Alarms
Isolated
4 - 20 mA
Retransmission
Non Isolated
4 - 20 mA
Retransmission
Display
Panel
96 * 96
All
All
Max. 4
Yes
Yes
4 digit max., ½" size
48 * 96
All
All
Max. 2
No
Yes
4 digit max, ½" size
72 * 72
All
All
Max. 2
No
Yes
4 digit max., ½" size

Note :: Serial and Parallel port can be provided only with 96 * 96 * 110 enclosure.